Single Phase
- Standard
- IEC 62053-21 · IEC 60252-11 · GB/T 17215-008 · PEA · MEA
- Display
- 6 Digit + 2 Decimal
- Voltage
- 200–250 Vac · 50 Hz
- Current
- Standard 15A(45A), 5A(100A)
Remote Cut-Off 15A(45A)
Prepaid 15A(45A) - Accuracy
- Class 1.0
Know the meter · Wire the right terminals · Choose the right lugs
Guide for 1-phase and 3-phase meters with RS485 communication
The specifications and standards listed above are as stated for this model/system, not a verified certification. Select equipment according to the actual model's nameplate and manual.
Left to right, separate from the power terminals
Signal wires must always be fitted with cord ends
Follow the actual model's manual for Pulse / COM wiring; this picture does not define it.
| Signal cable | Add a repeater at |
|---|---|
| Twisted pair 22 AWG | 30 devices or 30 m |
| Twisted pair + shield 18 AWG | 60 devices or 600 m |
Whichever comes first. This is a requirement of this system; the real usable distance depends on the equipment and site conditions.
Run the cable as a continuous daisy chain, separate from power cables. Follow the equipment manual for shielding and termination.
Terminal hole diameter
This is not the same as the cable cross-section in mm²
| Installation method | Cable cross-section |
|---|---|
| Free air | < 25 mm² Depends on model and load |
| In trunking | 35 mm² · lug required Depends on model and load |
Check that the lug fits the hole and tighten to the manufacturer's torque. Never force a cable into the terminal.
Install the stall's 2-pole CB after the meter: Lout and Nout go into the CB per this system's requirement
1-phase single-line diagram: wires that cross with a gap are not connected. This picture shows where the stall CB goes; it is not a full protection diagram of the installation.
Dust-protected to a level that does not affect operation
and protected against water splashing from any direction
Use a suitable roof or enclosure; avoid direct sun and areas near water. IP54 does not cover immersion or high-pressure water jets.
Not near taps, washing areas, standing water or flood zones. Never hose it down directly.
Provide shade and ventilation, keep away from heat sources, and check the temperature range in the manual.
Fit all covers and use suitable seals or cable glands. Leave no openings for water or dust.
Mount on a solid surface, away from impact and vibration, with room for inspection and repair.
Keep RS485 away from power cables and noise sources, and route cables so they don't pull on the terminals.
Check lugs, tightness and covers before energising. Look for signs of overheating at each maintenance round.